Trane furnace blinking red light: what each flash code means
Why It Stopped editorial team, updated

A Trane furnace reports faults by flashing a red light a set number of times, pausing, and repeating. On the XR80 (model TUD1), Trane's installer's guide lists 2 flashes as a lockout, 3 as a draft pressure error, 4 as an open temperature limit and 8 as a low flame signal. Slow and fast flashing without a count is normal. Codes differ a little between Trane furnace families, so check your model number first.
First, read the light correctly
Trane's furnaces signal with a light on the integrated furnace control (IFC), the circuit board that runs the start-up. Trane notes that on some furnaces you can see it from outside, while on others you only see it once the front panel is off.
- Slow flashing: normal, no call for heat.
- Fast flashing: normal, the thermostat is calling for heat.
- A counted group of red flashes, a pause, then the same group again: a fault code. Count at least three groups.
- Light on steady: Trane's chart says replace the control board.
- Light completely off: check power to the furnace.
Trane's homeowner guidance is to write down exactly what you see and not to take the front panel off while the furnace is running. Trane also notes that your unit may have a blower door switch that cuts power and gas when the door comes off.
Find your model family
The model number is on the rating plate inside the furnace. The first letters tell you which of Trane's tables applies. Trane's installer's guides note that the first letter can be T (Trane) or A (American Standard); the rest of the number is what matters.
| Model starts with | What it is | Which table |
|---|---|---|
| TUD1 / TDD1 | XR80, single-stage, 80% (Trane's product data lists the XR80 as TUD1) | XR80 codes |
| TUH1 / TDH1 | Single-stage condensing | Same codes, 9 flashes differs (see below) |
| TUH2 / TDH2 | Two-stage condensing with variable-speed inducer | Separate red and green lights (see below) |
If your number doesn't match any of these, search the full model number on Trane's literature library, or use the chart on the inside of the blower door. For any brand, our furnace blinking red light guide explains how to read an unfamiliar chart; we also cover York and Goodman codes.
XR80 flash codes (TUD1 and TDD1)
These come from Trane's installer's guide 18-CD19D7-29-EN, table 17, which covers the *UD1 and *DD1 fan-assisted furnaces.
| Flashes | What Trane's chart says | What it usually means for you |
|---|---|---|
| 2 | System lockout: retries or recycles exceeded | The furnace tried and gave up. See lockouts |
| 3 | Draft pressure error: venting, pressure switch or inducer problem | Check the vent pipes outside first. See 3 flashes |
| 4 | Open temperature limit circuit | The furnace got too hot; airflow first. See 4 flashes |
| 5 | Flame sensed when no flame should be present | Technician |
| 6 | 115-volt power reversed, poor grounding or system voltage too low | Electrician or technician |
| 7 | Gas valve circuit error | Technician |
| 8 | Low flame sense signal | Often a dirty flame sensor. See 8 flashes |
| 9 | Igniter relay fault | Technician |
| Steady on | Replace IFC | Control board, technician |
| Steady off | Check power | Breaker, furnace switch, door |
What the common codes mean, and what you can check
2 flashes: lockout
A lockout is the control giving up after repeated failures. On the XR80, Trane's guide explains that if the flame is lost during a heating cycle, the control retries ignition up to two times after the sensor cools; if it still can't light, it locks out. A power failure is different: when power comes back, the furnace restarts by itself if the thermostat still calls for heat.
Trane's homeowner page on hard lockouts lists the usual causes: a dirty or defective flame sensor, a faulty igniter, gas pressure problems, overheating, a dirty filter, blocked vent pipes or flue, and a faulty control board. Its advice is blunt: changing the air filter is the only fix you should try yourself.
3 flashes: draft pressure
Before the burners light, the inducer fan pulls air through the furnace and the pressure switch has to confirm the vent is drawing. Trane's guide says that if the pressure switch doesn't sense pressure, the gas valve won't open and the furnace won't start.
What you can check safely:
- The vent and air intake pipes outside. Snow, ice, a nest or leaves at the pipe ends can block them. Trane's condensing furnace guide says to check the vent and combustion air terminations for blockage and clear them.
- On a condensing (90%+) furnace, the condensate drain. Trane's *UH1 guide explains that a drain blocked by debris or ice signals the pressure switch, which stays open and won't let the unit run until the condensate flows freely again.
Testing the pressure switch, its tubing or the inducer motor is technician work.
4 flashes: open limit
The limit switch shuts the burners off when the heat exchanger gets too hot. On Trane's two-stage condensing guide, the same code also covers the rollout switch, which trips if flame escapes the burner area. Trane's XR80 guide notes there's a flame rollout device on the burner cover that shuts off all gas when it opens.
Too little airflow is the thing you can fix: replace a dirty filter (Trane suggests every 30 to 90 days, depending on the filter) and make sure the return air vents aren't blocked, as Trane's lockout page advises, and that supply registers are open. If the code comes back with a clean filter, or you suspect rollout, call a technician. Don't keep resetting a rollout switch: it opened because flame or heat escaped the burner area.
8 flashes: low flame signal
The burners light, but the board can barely detect the flame. Carrier names carbon buildup or oxidation on the flame sensor rod as the usual culprit when a furnace can't confirm its flame, and Trane's hard lockout page lists a dirty or defective flame sensor among the causes of lockouts. Our guide to a furnace blowing cold air explains how the sensor works and whether to clean it yourself.
5, 6, 7 and 9 flashes
These are electrical or gas valve faults with nothing for a homeowner to adjust: a flame signal when the gas should be off (5), wiring polarity, grounding or low voltage (6), the gas valve circuit (7), and the igniter relay on the board (9). Note the code and call.
Other Trane models
Trane's single-stage condensing guide (18-CD33D1-11-EN, *UH1 and *DH1) uses the same chart as the XR80 for 2 to 8 flashes. The difference is 9 flashes, which it describes as a check of the igniter circuit and of the voltage between line neutral and 24-volt common, a possible grounding problem.
The two-stage condensing guide (18-CD26D1-23-EN, *UH2 and *DH2) works differently:
| Light | Meaning |
|---|---|
| Green, slow flash | Normal, no call for heat |
| Green, fast flash | Normal, call for heat |
| Red, 1 flash every 20 seconds | Normal: LitePort data |
| Red, 2 flashes | Retries or recycles exceeded |
| Red, 3 flashes | Inducer or pressure switch error |
| Red, 4 flashes | Open limit or rollout switch |
| Red, 5 flashes | Flame sensed when no flame should be present |
| Red, 6 flashes | Line voltage reversed polarity |
| Red, 7 flashes | Gas valve circuit error |
| Red, 8 flashes | Weak flame |
| Red, 9 flashes | Open inducer limit |
| Green and red on steady | Fuse open or internal control failure |
On these models, the guide says the last four faults flash on the red light when power is turned on, newest first, with a two-second gap between them.
Resetting a lockout
Write the code down first: resetting the power clears the lockout, and you lose the clue. Trane's procedures differ by model:
- *Single-stage condensing (UH1): turn the power off, on, off and on again within 30 seconds, either at the furnace's power switch or at the thermostat. Trane's guide says it won't reset unless the full off-on-off-on sequence happens within 30 seconds.
- *Two-stage condensing (UH2): turn the power off for more than one second.
- Burner box limit (condensing models): Trane's guides say to check the vent and combustion air pipes outside first. If something was blocking them, clear it, and the reset button on the burner box may be pressed. If nothing was blocking them, the limit must be reset by a qualified servicer.
Reset once. If the same code comes back, the cause is still there, and Trane's own advice for a hard lockout is to call for service.
When to call a pro
Trane suggests telling the person who books the visit which lights or codes you saw and the furnace's brand and model. That helps the technician arrive with the right part. If the furnace shows no light at all, start with furnace not turning on; if it runs but keeps shutting off, see furnace short cycling. All furnace topics: furnace troubleshooting.
Questions people ask
What does 3 red flashes mean on a Trane furnace?
A draft pressure error. Trane's XR80 installer's guide lists three possible causes: a venting problem, a pressure switch problem or an inducer problem. On condensing models, Trane adds that a blocked or frozen condensate drain keeps the pressure switch open and stops the furnace. Check the vent and intake pipes outside for blockage; the switch and inducer are for a technician.
What does 2 red flashes mean on a Trane furnace?
System lockout: the furnace used up its retries or recycles. On the XR80, Trane's guide says the control retries ignition up to two times after a flame loss, then locks out. The lockout itself is the result; the cause is usually behind another code, such as a flame or gas supply problem.
How do I reset a Trane furnace after a lockout?
It depends on the model. Trane's guide for its single-stage condensing *UH1 furnaces says to turn the power off, on, off and on again within 30 seconds, at the furnace or the thermostat. Its two-stage *UH2 guide says power off for more than one second. Trane's homeowner advice is that a furnace in hard lockout needs a technician to find the cause, and that changing the filter is the only fix you should try yourself.
My Trane furnace light is flashing slowly. Is something wrong?
No. On the Trane furnaces covered here, a slow flash means normal operation with no call for heat and a fast flash means normal operation with a call for heat. Only a counted group of flashes with a pause between groups is a fault code.
Do American Standard furnaces use the same codes?
The Trane installer's guides used here cover model numbers whose first letter may be A or T, so an American Standard furnace with a matching model number (for example AUD1 alongside TUD1) uses the same table. Check the model number on your rating plate.
Sources
- Trane: XR80 product data, TUD1 models (PDF)
- Trane: Installer's guide 18-CD19D7-29-EN, *UD1/*DD1 fan-assisted furnaces, error flash codes (PDF)
- Trane: Installer's guide 18-CD33D1-11-EN, *UH1/*DH1 single-stage condensing furnaces (PDF)
- Trane: Installer's guide 18-CD26D1-23-EN, *UH2/*DH2 two-stage condensing furnaces (PDF)
- Trane: Furnace light blinking, what it means
- Carrier: Furnace flame sensor
- Trane: Furnace hard lockout, causes and solutions
Written by the Why It Stopped editorial team from the manufacturer manuals and safety guidance listed above. It covers checks a homeowner can do safely; gas lines, refrigerant and sealed components are work for a licensed technician. See our editorial policy, safety disclaimer and terms of use.
Other furnace problems

Furnace blinking red light: how to read what it's telling you
Count the flashes, find your model's chart, and see which group the code falls into.

Furnace blowing cold air: 8 causes and what to check first
Air moves but isn't warm: fan setting, filter, flame sensor, gas, condensate and ducts.

Furnace not turning on: 9 checks, in the order a tech would do them
Nothing happens at all: thermostat, power, filter, gas, vents, and lockout codes in order.

Furnace keeps turning on and off? How to tell what's causing it
Burners on and off every few minutes: filter, vents, thermostat, flue, then flame sensor, limit switch or an oversized furnace.

Goodman furnace error codes: what EE0, EE2, EE3 and the rest mean
EE0 to EE6, E10, E11, the blower and R-32 codes on current Goodman and Amana furnaces, from Goodman's service manuals.

York furnace red light blinking: what 1 to 11 flashes mean
Red, green and amber flash codes from York's TM9E manual, with soft and hard lockouts explained.